DIESEL GENERATOR SET
750-XC6DT2
750 kWe /60 Hz /Standby
208 - 4160V
(Reference 680-XC6DT2 for Prime Rating Technical Data)
SYSTEM RATINGS
Standby
Voltage (L-L)
Phase
PF
Hz
kW
kVA
Amps
skVA@30%
Voltage Dip
Generator Model*
Temp Rise
Connection
208V**
3
0.8
60
750
937.5
2602
2600
574RSL4037
130 °C/40 °C
12 LEAD LOW WYE
* Consult the factory for alternate configuration.
** UL 2200 Offered
240V**
3
0.8
60
750
937.5
2255
2600
574RSL4037
130 °C/40 °C
12 LEAD HI DELTA
380V
3
0.8
60
750
938
1426
1850
575RSL4044
130 °C/40 °C
4 BAR WYE
480V**
3
0.8
60
750
937.5
1128
2120
573RSL4035
130 °C/40 °C
12 LEAD HI WYE
600V**
3
0.8
60
750
937.5
902
3050
574RSS4278
130 °C/40 °C
4 LEAD WYE
4160V
3
0.8
60
750
937.5
130
1850
574FSM4358
130 °C/40 °C
6 LEAD WYE
CERTIFICATIONS AND STANDARDS
// Emissions – EPA Tier 2 Certified
// Generator set is designed and manufactured
in facilities certified to standards ISO 9001:2008 and
ISO 14001:2004
// UL 2200 / CSA – Optional
– UL 2200 Listed
– CSA Certified
// Performance Assurance Certification (PAC)
- Generator Set Tested to ISO 8528-5 for Transient Response
- Verified product design, quality and performance integrity
- All engine systems are prototype and factory tested
// Power Rating
- Accepts Rated Load in One Step Per NFPA 110
- Permissible average power output during 24 hours of
operation is approved up to 85%.