First Prev 11 12 13 14 15 16
Pin Functionality
Pin Number / Pin Name
1
-48V A
2
-48V B
3
Reserved
4
Reserved
5
RTN A
6
RTN B
7
ENA
8
ENB
9
C_CL-
10
HU-
11
HU+OUT
12
13
14
15
16
17
18
19
20
21
22
23, 24
25, 26
27, 28
29
30
HU+IN
ON/OFF-
ON/OFF+
B_OK#
A_OK#
A2
INTRPT
A1
SCL
A0
SDA
3V3 RTN
3V3 OUT
3V3 TRIM
12V RTN
12V OUT
ATC210 Dual Series | 210 W DC-DC
Intermediate Bus Converters
Function
Note
Power input from ‘A’ bus
Connects to ATCA Zone 1 connector pin 33 via external
10 A fuse
Power input from ‘B’ bus
Connects to ATCA Zone 1 connector pin 34 via external
10 A fuse
For future use
For future use
Power return from ‘A’ bus
Connects to ATCA Zone 1 connector pin 28 via external
12 A fuse
Power return from ‘B’ bus
Connects to ATCA Zone 1 connector pin 29 via external
12 A fuse
When connected to RTN A, turns ON
isolated open collector ‘A enabled’ device
(See Note 3)
Connects to ATCA Zone 1 connector pin 32 via external
1 A fuse. Used to signal to management system correct
board insertion and presence of ‘A’ bus
When connected to RTN B, turns ON
isolated open collector ‘B enabled’ device
(See Note 3)
Connects to ATCA Zone 1 connector pin 27 via external
1 A fuse. Used to signal to management system correct
board insertion and presence of ‘B’ bus
Connection to module of auxilliary
capacitor hold up array -ve
Utilises greater capacitance in a given can size of lower
voltage capacitors. Clamped to –50 V wrt HU+OUT
Connection to module of hold up
capacitor array -ve
Connection from on board filter and
management circuits to hold up
capacitor array +ve
May also connect to input of boost module to reduce
hold up storage area
Connection to main power converter from May also connect to output of boost module to reduce hold
hold up capacitor array +ve
up storage area
Current from pin to turn main output ON
Fully floating remote ON/OFF signal, may be used with
management system or ATCA ENABLE_A/B via R-D network
Current into pin to turn main output ON
Fully floating remote ON/OFF signal, may be used with
management system or ATCA ENABLE_A/B via R-D network
Open collector signal, monitors status of
“B” feed
Low when “OK”
Open collector signal, monitors status of
“B” feed
Low when “OK”
I2C lines, address strapping
Interrupt Alarm
I2C Register out of limits, LM80 pin ‘INT#’ direct connection
I2C lines, address strapping
Clock
I2C lines, clock line input
I2C lines, address strapping
Data
I2C lines, serial data
Management power return and I2C
Also return for ‘A _OK#’ and ’B_OK#’ signals.
Externally connected to ATCA Zone 1 connector pin 26
3V3, 6 W management power
Trim pin for management power
12 V return
Externally connected to ATCA Zone 1 connector pin 26
12 V power
Pin-Out Table