Parameters
Some parameters are not displayed depending on the
model of the Controller and parameter settings. For details,
refer to the E5CN/E5CN-U Temperature Controller User's
Manual (Cat. No. H129)
Adjustment Level
Press the Level Key less than 1 s.
Press the Level Key less than 1 s.
Power ON
Press the Level Key for at least 3 s.
(Display flashes for at least 1 s.)
Displays other than that for switching
between automatic and manual
Starting in manual mode
Manual Control Level
C
25 PID control only
Press the
Level Key
for at
PV/MV
least 1 s.
Starting in automatic
mode
Operation Level
Adjustment level
l.adj display
Displayed only once when
entering adjustment level.
a
at AT execute/cancel
off
a
cmwt Communications writing
off
a
ct1 Heater current value 1
0.0 monitor
a
ct2 Heater current value 2
0.0 monitor
a
lcr1 Leakage current value
0.0 1 monitor
a
lcr2 Leakage current value
0.0 2 monitor
a
hb1 Heater burnout 1
0.0 detection
a
hb2 Heater burnout 2
0.0 detection
a
hs1 SSR failure detection 1
50.0
a
hs2 SSR failure detection 2
50.0
a
C sp-0 SP 0
0
a
C sp-1 SP 1
0
a
SP used by multi-SP
C sp-2 SP 2
0
a
C sp-3 SP 3
0
a
C ins Temperature input shift
0.0
1-point shift
a
C
insh
0.0
Upper-limit
temperature
input
2-point
shift
a
C insl Lower-limit
0.0 temperature input
a
C
p Proportional band
8.0
a
i Integral time PID settings
233
a
d Derivative time
40
a
c-sc Cooling coefficient
1.00
a
Heating/cooling
C c-db Dead band
0.0
a
of-r Manual reset value
Clear the offset during stabilization
50.0 of P or PD control.
a
C hys Hysteresis (heating)
1.0
Hysteresis settings
a
C chys Hysteresis (cooling)
1.0
a
soak Soak time
1
a
C wt-b Wait band
off
a
mV-s MV at stop
0.0
a
mV-e MV at PV error
0.0
a
C sprt SP ramp set value
off
a
ol-h MV upper limit
105.0
a
ol-l MV lower limit
-5.0
a
Set either of these parameters.
Press the
Level
Key for at
least 3 s.
(Display
flashes
for at
least 1 s.)
C 25 Process value
Added when PV
display is added.
a
C 25 Process value/
0 set point
a Auto/manual switch
a-m
PID control only
Added when auto/manual
switching function is added.
a
m-sp Multi-SP set
0 point setting
a
C sp-m SP ramp monitor
0
a
ct1 Heater current value 1
0.0 monitor
a
ct2 Heater current value 2
0.0 monitor
a
lcr1 Leakage current
0.0 value 1 monitor
a
lcr2 Leakage current
0.0 value 2 monitor
a
prst Program start
rset
a
sktr Remaining soak
0 time monitor
a
r-s Run/stop
run
a
C al-1 Alarm value 1
0
a
C al1h Upper-limit
0 alarm value 1
a
C al1l Lower-limit
0 alarm value 1
a
C al-2 Alarm value 2
0
a
C al2h Upper-limit
0 alarm value 2
a
C al2l Lower-limit
0 alarm value 2
a
C al-3 Alarm value 3
0
a
C al3h Upper-limit
0 alarm value 3
a
C al3l Lower-limit
0 alarm value 3
a
o MV monitor (heating)
0.0
a
c-o MV monitor (cooling)
0.0
a
Press the Level + Mode
Keys for at least 3 s.
Display flashes.
Protect Level
Press the Level + Mode
Keys for at least 1 s.
Press the Level Key
less than 1 s.
Communications
Setting Level
The time taken to move to the protect level can
be adjusted by changing the "Move to protect
level time" setting.
Displayed only for models with communications.
Changes are effective after cycling power or after
a software reset.
pmoV Move to protect level
Displayed only when a password
0 is set. Restricts moving to protect
a
level.
Operation/adjustment
oapt protection
0
Restricts displaying and modifying
menus in operation, adjustment,
and manual control levels.
a
Initial Setting/
icpt Communications Protection
1
This protect level restricts movement
to the initial setting, communications
a setting, and advanced function
setting levels.
wtpt Setting change protection
off
Protects changes to setups by
operating the front panel keys.
a
pmsk Parameter mask enable
on
Displayed only when a
parameter mask is set.
a
prlp
0
Password to
protect level
move
to
Password setting
a
psel
Protocol setting
Switches between
cwf CompoWay/F
a (SYSWAY) and Modbus.
u-no Communications
1 Unit No.
a
CompoWay/F
bps
9.6
(SYSWAY) only
Baud rate
a
len Data bits
7
a
sbit Stop bits
2
a
prty Communications
eVen parity
a
sdwt Send delay
20
a
16
Digital Temperature Controllers E5CN/E5CN-U