DatasheetQ Logo
Electronic component search and free download site. Transistors,MosFET ,Diode,Integrated circuits

MS4 데이터 시트보기 (PDF) - Crydom Inc.,

부품명
상세내역
제조사
MS4 Datasheet PDF : 20 Pages
First Prev 11 12 13 14 15 16 17 18 19 20
Panel Mount Solid State Relays
Dual Relays, Quad Relays
120/240/480 Vac
SCR AC Switch Output
Industry Standard Package
Zero Cross or Random Turn-On
PSD
10-90Amp
120/240/480 Vac
Peak Switching
Internal Snubber
Two (Dual) or four (Quad) independent AC output relays come in a single standard
panel-mount package. Utilizing an AC switch output with internal snubber, relays
provide greater protection against false triggering. Model choices include zero
cross or random turn-on (phase controllable) switching (add suffix -10). For 24Vdc
Control (add suffix E). UL 508A SCCR Approved, consult Crydom for actual ratings.
Duals
Line
Voltage
Range
Vrms
D2425D 24-280
D2440D 24-280
H12D4825D 48-530
H12D4840D 48-530
Load
Current
Range
Arms
.15-25
.15-40
.15-25
.15-40
Control
Voltage
Range
Vdc
4-15
4-15
4-15
4-15
Control
Current
@ 5Vdc
mA
13
13
13
13
Must
Release
Voltage
Vdc
1.0
1.0
1.0
1.0
Surge
Current
1-Cycle
Apk
250
625
250
625
UL, CSA, VDE
UL, CSA, VDE
UL, cUL, VDE
UL, cUL, VDE
Quads
Line
Voltage
Range
Vrms
TD2420Q 24-280
TD2420Q-10 24-280
Load
Current
Range
Arms
.15-20
.15-20
Control
Voltage
Range
Vdc
4-15
4-15
Control
Current
@ 5Vdc
mA
12
12
Must
Release
Voltage
Vdc
1.0
1.0
Surge
Current
1-Cycle
Apk
250
250
UL, CSA
UL, CSA
Operating Temperature Range: -40˚C to 80˚C, Isolation Voltage: 4000 Vrms (Dual), 2500 Vrms (Quad)
53TP
25-50Amp 3 PHASE
120/240/480 Vac
SCR AC Switch Output
LED Status Indicator
Three-phase solid state relays switch up to 530 Vrms directly to loads such as
motors, transformers, heating elements, etc. Available with either AC or DC input
(coil) control in zero-voltage or random turn-on switching versions (add suffix -10).
For 24Vac Control (add suffix E).
Line
Voltage
Range
Vrms
D53TP25D 48-530
D53TP50D 48-530
D53DP25D** 48-530
D53DP50D** 48-530
Load*
Current
Range
Arms
.05-25
.05-50
.05-25
.05-50
Control
Voltage
Range
Vdc
3-32
3-32
4-32
4-32
Control
Current
@ 5Vdc
mA
10
10
20
20
Must
Release
Voltage
Vdc
1.0
1.0
1.0
1.0
Surge*
Current
1-Cycle
Apk
250
625
250
625
UL, CSA, VDE
UL, CSA, VDE
UL, cUL, VDE
UL, cUL, VDE
A53TP25D
Line
Voltage
Range
Vrms
48-530
Load*
Current
Range
Arms
.05-25
Control
Voltage
Range
Vrms
90-280
Control Must
Current Release
@ 120Vrms Voltage
mA
Vrms
2.2
10.0
Surge*
Current
1-Cycle
Apk
250
A53TP50D 48-530 .05-50 90-280 2.2
10.0 625
A53DP25D** 48-530 .05-25 90-280 5
A53DP50D** 48-530 .05-50 90-280 5
10.0 250
10.0 625
*Current and Surge Ratings are per phase.
** DP is two controlled phases with the third connected straight through (A1 - A2).
Operating Temperature Range: 40˚C to 80˚C, Isolation Voltage: 4000 Vrms
UL, CSA, VDE
UL, CSA, VDE
UL, cUL, VDE
UL, cUL, VDE
Output consists of an SCR AC switch turning on at the next peak of sinusoidal AC
wave form after the input has been activated. Continuing to conduct normally until
the input is deactivated and then turning off at the next current zero cross.
Suitable for switching transformers and other highly inductive loads where
significant inrush current may otherwise cause problems.
PSD2410
PSD2425
PSD2450
PSD2490
PSD4810
PSD4825
PSD4850
PSD4890
Line
Voltage
Range
Vrms
90-280
90-280
90-280
90-280
48-530
48-530
48-530
48-530
Load
Current
Range
Arms
.04-10
.04-25
.04-50
.04-90
.04-10
.04-25
.04-50
.04-90
Control
Voltage
Range
Vdc
3-32
3-32
3-32
3-32
4-32
4-32
4-32
4-32
Control
Current
@5Vdc
mA
2.0
2.0
2.0
2.0
8
8
8
8
Must
Release
Voltage
Vdc
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
Surge
Current
1-Cycle
Apk
120
250
625
1200
140
250
625
1200
UL, cUL
UL, cUL
UL, cUL
UL, cUL
Operating Temperature Range: -40˚C to 80˚C, Isolation Voltage: 4000 Vrms, Minimum Off-State dv/dt: 500V/μsec
Panel Mount - DC Output
DC60
3-7Amp
60 Vdc
DC Bipolar Output
AC or DC Control
Economical Panel Mount Package
The DC60 products provide bipolar transistor DC output switching with high
(4000 Vrms) isolation voltage. Only Crydom offers AC input/DC output relays in this
economical standard panel-mount package.
DC60S3
DC60S5
DC60S7
Line
Voltage
Range
Vdc
3-60
3-60
3-60
Load
Current
Range
Adc
.02-3
.02-5
.02-7
Control
Voltage
Range
Vdc
3.5-32
3.5-32
3.5-32
Control
Current
@ 5Vdc
mA
2.2
2.2
2.2
Must
Release
Voltage
Vdc
1.0
1.0
1.0
Surge
Current
1 sec.
Adc
6
10
14
UL, cUL
UL, cUL
UL, cUL
DC60SA3
DC60SA5
DC60SA7
Line
Voltage
Range
Vdc
3-60
3-60
3-60
Load
Current
Range
Adc
.02-3
.02-5
.02-7
Control
Voltage
Range
Vrms
90-280
90-280
90-280
Control Must
Current Release
@120Vrms Voltage
mA
Vrms
2
10
2
10
2
10
Operating Temperature Range: -30˚C to 80˚C Isolation Voltage:4000 Vrms
Normally closed (Form B) versions available (-B suffix)
Surge
Current
1 sec.
Adc
6
10
14
UL, cUL
UL, cUL
UL, cUL
Other Crydom products and competitive part number cross-reference available at: www.crydom.com
11

Share Link: 