DatasheetQ Logo
Electronic component search and free download site. Transistors,MosFET ,Diode,Integrated circuits

CA3272A 데이터 시트보기 (PDF) - Intersil

부품명
상세내역
제조사
CA3272A Datasheet PDF : 10 Pages
1 2 3 4 5 6 7 8 9 10
CA3272A, CA3292A
The output will continue to turn on and off for as long as the
shorted condition exists or until shutdown by the input logic.
The resulting frequency and duty cycle of the output current
flow is determined by the ambient temperature, the thermal
resistance of the package in the application and the total
power dissipation in the package. Since each output is inde-
pendently protected, the frequency and duty cycle of the cur-
rent flow into multiple shorted outputs will not be related in
time. Long lead lengths in the load circuit may lead to oscilla-
tory behavior if more than two output loads are shorted.
FAULT SENSE
VBATT
4V
THRESHOLD, VTHD
ZENER
CLAMP
TLIM
ZA
QA
RLOAD
2
OUT A
IO(SINK)
ILIM
0.02
FIGURE 3. OUTPUT OPEN LOAD DETECTION WHERE IO(SINK)
IS AN ACTIVE CURRENT SINK PULLDOWN FOR
OPEN-LOAD FAULT DETECTION. THE CURRENT
ICEX IS IO(SINK) PLUS LEAKAGE CURRENTS OF
THE OUTPUT DRIVER
Since a diagnostic flag indicates when an output is shorted,
this information can be used as input to a microprocessor or
dedicated logic circuit to provide a fast switch-off when a
short occurs and, by sequence action, can be used to deter-
mine which output is shorted. A fault condition in any output
load will cause the FAULT output to switch to a logic “low”.
Since a fault condition may be detected during switching,
use of an appropriate size capacitor to filter the FAULT out-
put is recommended. The recommended FAULT output cir-
cuit is shown in Figure 2. This will prevent the FAULT output
voltage from reaching a logic level “0” within the maximum
switching time.
The FAULT detection circuitry compares the state of the
input and the state of the output for each A, B, C and D
channel. The output is considered to be in a high state if the
voltage exceeds the typical FAULT threshold reference volt-
age, VTHD of 4V. If the output voltage is less than VTHD, the
output is considered to be in a low state. For example, if the
input is high and the output is less than VTHD, a normal
“ON” condition exists and the FAULT output is high. If the
input is high and the output is greater than VTHD, a shorted
load condition is indicated and the FAULT output is low.
When the input is low and the output is greater than VTHD, a
normal “OFF” condition is indicated and the FAULT output is
high. If the input is low and the output is less than VTHD, an
open load condition exists and the FAULT output is low. The
Output Driver Fault Sense state is determined by high and
low comparator threshold limits which are defined in the
Fault Parameters section of the Electrical Specifications.
The FAULT output diagram of Figure 2 shows the circuit
component interface for sensing a diagnostic fault condition.
As noted, the time constant of TX = RXCX should be greater
than the ON-OFF output switching times to avoid false fault
readings during switching. For applications requiring fast
period repetition rates, the maximum time constant should
be significantly less than the period of switching. The short-
est practical time constant is preferred to limit the duration of
a fault condition.
To match a standard CMOS or TTL interface, the switched
current at the FAULT pin must be converted to VIH and VIL
voltage levels using the RX external pullup resistor. The min-
imum specified IOL limit at the FAULT output defines the Low
(Fault) state which is used to test for a VOL maximum limit of
0.4V. This makes the calculation for the VIL input level rela-
tively simple. Where VF is the FAULT output voltage, VCC is
the power supply voltage, RX is the pullup resistor to VCC
from the FAULT pin and IOL is the fault condition sink cur-
rent, IO(SINK), the low state equation is:
VF = VCC - RXIOL VIL
(EQ. 1)
As an example: Since TTL is the worst case for a low state,
VIL = 0.8V. Using VCC = 5V, maximum VF = VOL = 0.4V and
minimum IOL = 1mA for the CA3272A and CA3292A. At the
worst case limit, the minimum value of RX is:
RX = (VCC - VIL)/IOL = (5 - 0.4)V/0.001mA = 4.6k
The preferred value for RX would be greater than the values
calculated.
For the logic VIH High (normal state),
VF = VCC - RXIOH VIH
(EQ. 2)
Where the IOH current is the specified leakage current,
IF(LK) at the FAULT pin, it remains to check the calculated
value for RX as a leakage current times the chosen pullup
resistance. To determine that the minimum VOH from the
FAULT pin is greater than VIH to an external logic match, VF
is calculated using Equation 2. For example, using the mini-
mum RX resistor value calculated for the CA3272A,
VF = [5 - (4.6kx 20µA)] = 4.9V
which is more than suitable for CMOS or TTL Input switching
levels; suggesting that a larger value of RX (such as 10kΩ)
could be used for a better noise margin in the Low fault state.
To detect an open load, each output has an internal low-level
current sink, shown in Figure 3, which acts as a pull-down
under open load fault conditions and is always active. The mag-
nitude of this current plus any leakage associated with the out-
put transistor will always be less than 100µA. (The data sheet
specification for ICEX includes this internal low-level sink cur-
rent). The output load resistance must be chosen such that the
voltage at the output will not be less than VTHD when the ICEX
sink current flows through it under worse case conditions with
minimum supply voltage. For example, assume a 6.5V mini-
mum driver output supply voltage, a FAULT threshold reference
voltage of VTHD = 5.5V and an output current sink of
ICEX = 100µA. Calculate the maximum load resistance that will
not result in a FAULT output low state when the output is OFF.
6

Share Link: 

datasheetq.com  [ Privacy Policy ]Request Datasheet ] [ Contact Us ]