FOR CURRENT OUTPUT:
• Connect a digital milliampmeter or equivalent, across the current output terminals.
• On the PCA-121 select the “Coarse Range Adj” that corresponds to the maximum input
frequency. Refer to Table - 1 for selection options.
• Adjust “4mA ADJ” control for desired “Zero” current (i.e. 4mA).
• Inject the full-scale test frequency while adjusting “20mA ADJ” for current equal to SET (SPAN).
• Iterate above steps until no change is observed.
FOR VOLTAGE OUTPUT:
NOTE: For proper adjustment of the voltage-output, First
Perform calibration of the current output.
• Connect a digital voltmeter across the voltage output terminals.
• On the PCA-121 select the “Coarse Range Adj” that corresponds to the maximum input
frequency. Refer to Table -1 for selection options.
• Adjust “VO ADJ” for 0.00 volts).
• Inject the test frequency while adjusting “VFS ADJ” for voltage equal to SET (SPAN).
• Iterate above steps until no change is observed.