1500W Single Output Power Supply
RSP-1500 series
2.Alarm Signal Output
(1)Alarm signal is sent out through "P OK" & "P OK GND" pins
(2)An external voltage source is required for this function. The maximum applied voltage
is 50V and the maximum sink current is 10mA
(3)Table 2.1 explain the alarm function built-in the power supply
Function
Description
Output of alarm(P OK)
P OK
The signal is "Low" when the power supply is above
65% of the rated output voltage-Power OK
The signal turns to be "High" when the power supply
is under 65% of the rated output voltage-Power Fail
Low
(0.5V max at 10mA)
High or open
(External applied voltage
10mA max.)
Table 2.1 Explanation of alarm
P OK
0.1uF 100K
R
V
P OK GND
External voltage and R
(The max. Sink is 10mA and 50V)
Fig. 2.2 Internal circuit of P OK (Open collector method)
3.Output Voltage TRIM
(1)Adjustment of output voltage is possible between 70~100%(Typ.) of the rated output which is shown in Fig. 3.1
(2)Connecting a resistor externally between TRIM and-S on CN1 or CN2 that is shown in Fig. 3.2.
Vout
100%
90%
80%
70%
R
0
470 1.8K OPEN
Fig. 3.1 External Resistor (Typical)
TRIM
CN1
or
CN2 -S
R(0.5W)
Fig. 3.2 Output voltage trimming
4.Current Sharing
(1)Parallel operation is available by connecting the units shown as below
(+S,-S and LS are connected mutually in parallel):
(2)The voltage difference among each output should be minimized that less than 2% is required
(3)The total output current must not exceed the value determined by the following equation
(Output current at parallel operation)=(The rated current per unit) x (Number of unit) x 0.9
(4) In parallel operation 4 units is the maximum, please consult the manufacture for other
applications
(5) When remote sensing is used in parallel operation, the sensing wire must be connected only
to the master unit
No.1(Master)
AC/L AC/N
No.2(Slave)
AC/L AC/N
V+
+S
-S CN1
LS
V-
+S
-S CN2
LS
V+
+S
-S CN1
LS
V-
+S
-S CN2
LS
No.3(Slave)
AC/L AC/N
V+
+S
-S CN1
LS
V-
+S
-S CN2
LS
+S +V
Load
-V
-S
No.4(Slave)
AC/L AC/N
V+
+S
-S CN1
LS
V-
+S
-S CN2
LS
File Name:RSP-1500-SPEC 2007-03-19