DatasheetQ Logo
Electronic component search and free download site. Transistors,MosFET ,Diode,Integrated circuits

ADPRF 데이터 시트보기 (PDF) - Gamewell-FCI by Honeywell

부품명
상세내역
제조사
ADPRF
GAMEWELL-FCI
Gamewell-FCI by Honeywell GAMEWELL-FCI
ADPRF Datasheet PDF : 2 Pages
1 2
Description (continued)
Remote alarm annunciation can be accomplished by using
the RA400Z remote annunciator or the RTS451or
RTS451KEY remote test station. Both these devices allow
testing of the sensor from a remote location.
ADPF low-flow duct sensors are designed for simplified
installation and easy maintenance. The modular construc-
tion allows for easy cleaning and uncomplicated field
replacement of the UL recognized power and sensor
boards.
The ADPF (non-relay) has outputs for a remote LED dis-
play and remote test switch. It incorporates zener diodes
to conserve power for communications to other devices.
The ADPF is a 2-wire device that requires signaling line
circuit power only.
The ADPRF (with relay) has powered outputs for remote
LED indication with a remote test switch and audible
sounder. Two form “C” auxiliary contacts can be config-
ured as a relay version or jumpered to mimic the non-relay
version. It has a patented cover tamper trouble signal. The
ADPRF is a 4-wire device that requires both signaling line
circuit power and either 24VAC/DC or 120/240VAC for
proper operation.
Specifications
Operating Temperature
Operating Humidity
Range:
Storage Temperature
Range:
Duct Air Velocity:
Shipping Weight:
Dimensions
Length:
Width:
Depth:
32° to 131° F (0° to 55° C)
10 to 93% relative humidity
(non–condensing)
-22° to 158° F
(-30° to +70° C)
100-4000 ft./min.
(0.5—20.32 m/s)
ADPF: 3.35 lbs. (1.5 kg)
ADPFRF:3.90 lbs. (1.8 kg)
14 3/4” (37 cm)
5 1/2” (14 cm)
2 3/4” (7 cm)
Model ADPF (Non-relay)
Voltage Range:
15 to 32 VDC
Standby Current:
300 µA @ 24 VDC
(one communication every 5
seconds with LED flash
enabled)
Model ADPFRF (with Relay)
Current Requirements (using no accessories)
Power
Supply Voltage: 20-30 VDC 30 VAC,
120 VAC, 22/240 VAC,
Max. Standby
Current:
26 mA
50-60 Hz 50-60 Hz 50-60 Hz
65 mA RMS 44 mA RMS 25 mA RMS
Max. Alarm
Current:
87 mA 182 mA RMS 52 mA RMS 30 mA RMS
Alarm Response
Time:
3 to 10 sec. 3 to 10 sec. 3 to 10 sec. 3 to 10 sec.
Auxiliary Relay Contact Ratings
Alarm auxiliary contacts* (DPDT):
10 A @ 30 VDC
10 A @ 277 VAC (0.75 power factor)
240 VA @ 249 VAC (0.4 power factor)
1/8 HP @ 120 VAC
1/4 HP @ 240 VAC
Supervisory contact (SPST):
2.0 A @ 30 VDC (resistive)
Minimum switching current for auxiliary contact must be
100 mA DC minimum @ 5 VDC.
Accessory Current Loads at 24 VDC
Device
Standby
Alarm
PA400
RA400Z
RTS451/
0 mA
0 mA
0 mA
15 mA Max.
12 mA Max.
10 mA Max.
RTS451KEY
Ordering Information
Part Number Description
ADPF
Analog addressable low-flow photoelec-
tronic non-relay duct smoke sensor
ADPRF
Analog addressable low-flow photoelec-
tronic with relay duct smoke sensor
ST-1.5
Sampling tube duct widths 1’-2’
ST-3
Sampling tube duct widths 2’-4’
ST-5
Sampling tube duct widths 4’-8’
ST-10
Sampling tube duct widths 8’-12’
A5060
Replacement power board for ADPF-RF
(w/relay)
A5067
Replacement power board for ADPF
(w/o relay)
Accessories Description
RTS451
Remote test station
RTS451KEY Remote test station w/key
RA400Z
Remote LED
F36-09-11 Replacement filters
M02-04-00 Test magnet
P48-21-00 End cap of metal sampling tube
P48-61-00 End cap for plastic sampling tube
S08-39-01 Replacement photo insect screen
GAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118
9020-0622 Rev. C page 2 of 2
www.gamewell-fci.com

Share Link: 